Study of the ferroresonance risk on an industrial site

You can contact the CAPSIM's specialist of this activity:
   - By email
   - By phone: +33 (0)4 42 63 61 18

Validation of a transformer model (test of the vacuum switching current)
Validation of a transformer model (test of the vacuum switching current)
Requirement:
As part of the connection of a 63/20 kV transformer station supplying a gas compression plant, CAPSIM investigated the risk of ferroresonance on the site.

Realization:
An initial theoretical characterization step of the risk on the site was performed (analytical approach).
Next, the various pieces of equipment which have an influence on the ferroresonance risk were modelled using an electromagnetic-transient analysis software. In particular, thorough modelling of the transformer was undertaken in collaboration with the manufacturer in such a way as to precisely represent the saturation and remnant flux phenomena.
As a function of the structure of the power grid, simulation was used to identify the risk configurations and conditions, and a risk analysis was formalized.

Results:
Several solutions have been proposed, from both an operating and design point of view, allowing the appearance of ferroresonance on the power grid to be avoided.

Ferroresonance phenomena on the primary voltages
Ferroresonance phenomena on the primary voltages